发电厂电气部分第四版熊信银
- 格式:doc
- 大小:152.50 KB
- 文档页数:4
发电厂电气部分例题
6-10(P214)设发电机容量为25MW ,I N =1718A ,最大负荷利用小时T max =6000h ,三相导体水平布置,相间距离
a=0.35m ,发电机出线上短路持续时间t k =0.2s ,短路电流I"=27.2A ,2/t k I =21..9kA,k t I =19.2kA,周围环境温度400C 。试选择发电机引出导线。 衬垫
,每跨绝缘子中设一个则取且满足)
(导体不发生共振的,)(截面系数则相间应力)(同相条间应力,取临界跨距式之间的截面形状系数、)得条(查图动稳定校验:
,热稳定合格。
)()得(查表)()
(时温度校正系数)(,查附表,长期允许载流量)竖放,(选)(查附表)得经济电流密度(查图,则选硬铝矩形导体续工作电流)导体所在回路最大持解:(m 1L ,L L L L m .02275
.33103.611071606.53m EJ f N L )
m (1063.112
125.001.012bh J ,375.3270001.0125.0b h m )
m (17.1f W 10L )m /N (5.264835.0/102.731073.1a /i 1073.1f 101.8h 1.44b W )Pa (102010)5070(Pa 105001
.0125.025.04956h b 2L f W M ,
m 5.0L )m (71.0f h
b L )666206P )(m /N (495610b 1i K 5.2f 7.30K 2175P 103,074.0b
h b b 2,08.012510h b )kA (2.732.2729.1I" 2k ish 101252)mm (2500mm 2015.4110.424694
1
k Q C 1S 94C 205P 126)C (8.531804
)171805.1()4070(40I I 73P s 246.4(kA)14898.4 TI")I 10I (I"12t
Q Q Q
1.80K C 40355P 3 )A (9.1803I )A (2658328281.0KI I I A
3282I 45.1k 101252 354P 1 )mm (265368
.09.1803J I S 8
.60J 205P 176,h 6000T 4000A )A (9.1803171805.1I 05.1I 1max 'max 6101f max '
4633m ph
ph max 2
37sh 27ph 5
-266b al ph 6
2
222
b b b b b b
4cr 8sh 212b 12sh 226f k min 0
2
2al 2max 20l a 022t 2/2t 22k np p k 0max C 40al f 2max max N max k k 0=<<=⨯⨯⨯⨯===⨯=⨯===⨯⨯=ρ⨯⨯==σ=
=⨯⨯⨯=⨯⨯=⨯==⨯=⨯-=σ-σ=σ⨯=⨯⨯⨯===σ==⨯λ=-=⨯==-=+-===⨯⨯==⨯⨯=<=⨯⨯⨯===-=⨯⨯-+=θ-θ+θ=θ⋅=+=+++=+===>=⨯=====⨯⨯====-=<=⨯==-----(P214)6-11、选择100MW 发电机和变压器组之间母线桥的导体。已知发电机回路最大持续工作电流I max =6791A ,T max =5200h ,连接母线三相水平布置,相间距离a=0.7m ,最高温度350C ,母线短路电流I"=36kA,短路热效应Q k =421.1(kA)2.s 。
衬垫
,每跨绝缘子中设两个则取且满足)
(导体不发生共振的,导体惯性矩查附表)(,
,导体截面系数查附表取)
(,)动稳定校验:
(,满足热稳定。
)()()得(查表(热稳定校验:
,则时温度修正系数),(查附表,导体载流量槽铝导体截面积为,选双
查附表)(),槽型母线(选择截面,查图按经济电流密度
,所以选槽型铝导体,工作电流)发电机回路最大持续解:(m 5.1L ,L L L L m 74.1816
.21102941071606.53m E J f N L )m (10294J 2),m /kg (816.212700108080108080m )
m (26.5f W 10L ),m /N (8.23157.0/10.8961073.1a /i 1073.1f )
Pa (1095.681005.11070)Pa (1005.110105.462.05.0)108.96(16.410hW L i 6.14m 105.46cm 5.46W W 2,m 5.0L m /N .623422
.01
)108.96(105h 1i 105f )kA (8.963629.1"I 2k i 3mm 8800mm .6253237.1101.42190
1
k Q C 1S 205P ,90C P205126C 6277446791)3570(35I I ))2().A (6719)A (7744880088.0KI I I 8.80K C 35355P 3,,mm 90b ,mm 200h A 8800I ,237.1k ,mm 80802),mm (893667
.06791
J I S ,mm /A 6.70J 205P 176,h 5000h 5200T A 6791I 1max 'max 8101f max '
486m 6ph
ph max 2
37sh 27ph 6
66b al ph 6962239Y 2b 2sh b 363Y b 2382sh 8b sh sh 226f k min 02
2
2al
2max 0al 0C 35al 0f 22max min 2max max 0=<<=⨯⨯⨯⨯===⨯==⨯⨯=ρ⨯⨯==σ=
=⨯⨯⨯=⨯⨯=⨯=⨯-⨯=σ-σ=σ⨯=⨯⨯⨯⨯⨯⨯=⨯=σ⨯=====⨯⨯⨯⨯=⨯==⨯⨯==<=⨯⨯⨯===-=⨯-+=θ-θ+θ=θ>=⨯============->==------------
(P133)4-10、某220kV 系统的重要变电站装置2台120MV ·A 的主变压器,220kV 侧有4回进线,110kV 侧有10回进线且均为Ⅰ、Ⅱ类负荷,不允许停电检修出现断路器,应采用何种接线方式?画出接线图并简要说明。 解:
WL1 WL2 WL3 WL4
WP1 QFP1
220kV QFC1
T1 T2
110kV
QFC2
5回…… QFP2 ……5回
WP2
(P133)4-11、某新建地方热电厂有2×25MW+2×50MW 共4台发电机,8.0cos =ϕ,U N =6.3kV,发电机电压级有10条电缆馈线,其最大综合负荷为30MW ,最小为20MW ,厂用电率为10%,高压侧为110kV ,有4回线路与电力系统相连,试初步设计该厂主接线图,并选择主变压器台数和容量。主接线图上应画出各主要设备及馈线,可不标注型号和参数。
解: WL1 WL2 WL3 WL4 WP
⎪⎩⎪⎨⎧=(发电机出口处)(变压一回线))(远离发电厂或较远处其中
1.9 5.81 .81k sh